Homepage‎ > ‎Sensoren‎ > ‎

SDM530C 3-FASIG


 Meter type 

 SDM530C
 Nominal voltage (Un) 
 230/400V AC (3~) 110/220V AC
 Insulation capabilities
- AC voltage withstand
- Impulse voltage withstand
 4KV for 1 minute
6KV – 1.2µS waveform
 Basic current (Ib)
- CT type
- Directly connect
 5 A
10A
 Maximum rated current (Imax)
- CT type
- Directly connect
 6A
100A

 Operational current range  0.4% Ib- Imax
 Over current withstand  30Imax for 0.01s
 Operational frequency range  50Hz ±10%
 Internal power consumption 

 ≤2W / 10VA per phase
 Test output flash rate (PULSE LED)
- CT type
- Directly connect
 1600imp/kWh
400imp/kW
 Test pulse output rate (pins 8 & 9)
- CT type
- Directly connect
1600imp/kWh
400imp/kWh
 CT Changing-Ratio 27 ratios optional
 Phase voltage missing indicator
(Phase A,B & C LED)
 LED turn on when the phase voltage is
missing
 Consumption indicator  (PULSE&SO LED) Flashing at load running
 Communication indicator  Flashing at communication running
 Data communication port  RS485 and far infrared
 Data save  The data can be stored more than 20 years
when power off